7.14  Email Notification of Alarms

Email notification of Alarms is a standard feature in Advantech WebAccess/SCADA. No third party software is required. Tags can be individually selected to generate an email, assigned recipient email address or use global email recipients. Alarms can be acknowledged via a reply email.

Advantech WebAccess/SCADA uses an SMTP Server to send Emails. The default is to use and SMTP (Simple Mail Transfer Protocol) installed as part of IIS on the Project Node. During node software installation, a SMART HOST is specified that allows the SMTP server on the Project Node to forward emails outside its domain.

The SMTP Server name is specified as the Outgoing Email Server part of SCADA Node Properties.

It is recommended to use the Project Node as the Outgoing Email server for all SCADA Nodes and configure the SMTP service on the Project Node to use your company's Email Server as a SMART HOST.

Pager and Wireless PCS Alarm messaging 

Pagers, wireless PCS and Cell Phones that can receive text messages can also be used for notification of Alarms and events. No third party software is required. Tags can be individually selected to generate an email message to a specific recipient address or use global recipients. The pager or wireless PCS must be able receive emails (a standard feature with Skytel and most Pager services).

Schedule Alarm Email recipients by Shift, Day of Week, and Holidays

The scheduler can schedule different email recipients based on Time of day, shift, Day of Week, and Holiday schedules.

Reply Email to Acknowledge Alarms

The Alarm Notification Email can contain a message to enable a reply email to acknowledge the alarms.

An Incoming Email Server (POP3 server), account name and password must be configured for the SCADA Node Properties  to retrieve the incoming emails. Reply Alarm Email to Ack must also be enabled on the SCADA Node.

The default Alarm email is of the following form:

 

From: scadanode1@cwo.com [mailto:scadanode1@cwo.com]

Sent: Saturday, January 25, 2003 6:05 PM

To: Tom Carter

Subject: compressorrpm - Low-Low Alarm

Low-Low Alarm (0.00)

KMC RTU11 compressor speed

%ack_begin_LiveDemo_SCADAnode1_67.94.27.175%

compressorrpm

%ack_end%

 

The Alarm Acknowledgement is of the following form

 

%ack_begin_Projectname_Nodename_NodeAddress%

tagname

%ack_end%