7.7        Alarm Groups

An Alarm Group is typically a process unit in a multi-process plant.

An Alarm Group Display summarizes alarm events for a fixed and limited number of tags (100 tags maximum in an Alarm Group, up to 9999 Alarm Groups).  In contrast, the Alarm Summary displays all active and unacknowledged alarms in reversed chronological order.

Alarm Groups can be configured in any logical arrangement. These are user configurable.

The information provided for each tag includes the alarm priority, date and time of the alarm, alarm type, Alarm Limit, value, and status of the alarm.

The Alarm Group Displays use a pre-built template display.  Alarm Groups are easily configured, by typing the Tagname in a list.  Alarming does not need to be enabled to add a tag to an alarm group.

Alarm Disable/Enable pushbutton is provided on the Alarm Group.  This is intended to allow a operators to Disable Alarms for a Unit that is shutdown or out of service, thereby eliminating nuisance alarms.

The Alarm Group List is a Popup Dialog Box showing all configured Alarm

Groups.

The Alarm Group List can be viewed from the Toolbar icon  or F6 function key or a pushbutton with the <DIALOG>ALMGROUP keymacro. 

The Alarm Group List  can also be called using the Right-Click Menu
 (Right Click->Goto->Alarm Group)

and from the Point Goto Dialog Box.  An alarm group can be called directly from a Pushbutton with the <GOTO>ALMGROUP=group number keymacro.

Power Users, General Users and the admin account can view Alarm Groups through a Web Browser. (Restricted users cannot view Alarm Groups through a Web Browser). All users can view Alarm Groups locally on the SCADA node using ViewDAQ.

The Alarm Group Display is a pre-built template display supplied with Web Access. It can be customized by engineers and technicians using DRAW.  How your Alarm Group Colors, Flashing, Fonts, etc. behave may vary based on how (or if) the Almgrp.Bxx (and Almgrp.dxx) on your system is modified.

 

Figure 7.5 Alarm Group

Alarm E/D

Pressing the Alarm Enable /Disable pushbutton will disable alarming for the selected tag (temporarily). 

The alarming will be disabled until the Alarm E/D pushbutton is presses again, the .ALMED tag field is changed or the SCADA node Restarts.

To Disable or Enable Alarming for a Tag from the Alarm Group Display:

1.      Select the Tagname (or anywhere on the same line)

2.      Select ALARM E/D pushbutton.

 

Acknowledge Screen

Pressing the Acknowledge Screen button will acknowledge all active alarms Displayed on the screen. 

If there are more than 17 alarms (i.e. the number that will fit in the Alarm Group Display at one time), only the first 17 alarms will be acknowledged. The user must use the Scroll Down (or Scroll UP) buttons to view additional Alarms, which will be unacknowledged.

Acknowledge Tag

Pressing the Acknowledge Tag button will acknowledge only the selected tag.  To acknowledge only one tag on the Alarm Group:

1.      Click on the Tagname (or anywhere on that line)

2.      Click Acknowledge Tag

Acknowledge Group

Pressing the Acknowledge Group pushbutton will acknowledge all active Alarms in the Alarm Group of the Selected Tag. There can be up to 100 Tags in an Alarm Group.

Group No.

Indicates the Alarm Group Number. There can be an unlimited number of Alarm Groups.

Current Value

Indicates the current value of the selected Tag.

Tag Description

Displays the description of the Selected Tag.